12 WIKA operating instructions pressure transmitter model A-10
11218720.10 01/2012 GB/D/F/E
GB
3.4 Accuracy
The model A-10 is optionally available with an improved non-linearity. Depending on the version the
following values apply.
Non-linearity per BFSL (IEC 61298-2) Standard
≤ ±0.5 % of span
Option
≤ ±0.25 % of span
Non-repeatability ≤ 0.1 % of span ≤ 0.1 % of span
Long-term drift (per IEC 61298-2) ≤ ±0.1% of span ≤ ±0.1% of span
Signal noise ≤ ±0.3% of span ≤ ±0.3% of span
Settling time < 4 ms < 4 ms
Temperature error at 0 ... 80 °C Typical: 1 % of span
Maximum: 2.5 % of span
Typical: 1 % of span
Maximum: 2.5 % of span
Measuring deviation of the zero signal Typical: ≤ ±0.5 % of span
Maximum: ≤ ±0.8 % der Spanne
Typical: ≤ ±0.15 % of span
Maximum: ≤ ±0.4 % of span
Accuracy at room temperature
1)
≤ ±1 % of span ≤ ± 0.5 % of span,
≤ ± 0.6 % of span (at 0 ... 5 V)
1) Including non-linearity, hysteresis, zero oset and end value deviation (corresponds to measured error per IEC 61298-2). Calibrated in
vertical mounting position with process connection facing downwards.
3. Specications
3.6 Operating conditions
Ingress protection (per IEC 60529)
The ingress protection depends on the type of electrical connection (see table under 3.7 "Electrical
connections, specications").
Vibration resistance
10 g (IEC 60068-2-27, under resonance)
20 g available on request
Shock resistance
500 g (IEC 60068-2-6, mechanical)