11WIKA operating instructions pressure transmitter, model MHC-1
14035467.01 08/2012 GB/D/F/E
GB
3. Specications
Temperature error
The model MHC-1 is temperature compensated in the range from -40 ... +85 °C.
Temperature range 0 ... 60 °C: ≤ 0.5 % of span
Temperature range -20 ... +85 °C:
≤ 1 % of span
Temperature range -40 ... 0 °C: ≤ 1 % of span
Settling time
≤ 1.5 ms (Baud rate ≥ 125k)
Long-term stability
≤ ±0.2 % of span/year
3.6 Operating conditions
Ingress protection (per IEC 60529)
IP 6K9K
The stated ingress protection only applies when plugged in using a mating connector that has the
appropriate ingress protection.
Vibration resistance (per IEC 60068-2-6)
20 g
Shock resistance (per IEC 60068-2-27)
500 g
Service life
> 10 million load cycles