GB
5. Installation and commissioning ... 6. Measuring arrangements
Liquid media Gaseous media
Contents of
tailpipe
Liquid Liquid with
vapour
Vapour
only
Gas only Wet gas Liquid gas
conden-
sate
Typically
Condensate Boiling liquid Liquefied gas Dry air Moist air,
Flue gas
Steam
Pressure
instrument
higher than
tapping point
Pressure
instrument
lower than
tapping point
11297264 05/2009 GB/D/F/E
WIKA Operating Instructions intelliGAUGE family 13
Once the pressure and electrical connections have been made, the transmitters
are ready for immediate use.
The A-VA-1 type or KFA6-STR-1.24.500 type feed units may be used to provide
the standard transmitter with DC voltage.
No attempt should be made to remove a pressurised instrument. If the trans-
mitter cannot be otherwise isolated, the pressure system must be fully vented.
The clamping screws on the top and bottom flanges of diaphragm element
pressure gauges must not be unscrewed.
Any residual pressure medium contained in the pressure
element may be hazardous or toxic. This should be taken into
account when handling and storing pressure gauges which
have been removed.
Pressure connection
In accordance with the general technical regulations for pressure gauges (e.g.
EN 837-2 "Selection and installation recommendations for pressure gauges").
6. Measuring arrangements
Proven measuring arrangements for various types of media.