14. CSA-чертеж установки
Notes
1
Install per Canadian ElectricalCode (Part 1) and local codes, as applicable
2
Associated apparatus (barrier) must be entity -certified by CSA, used in an
certified configuration and installed in accordance with barrier manufacturer's
instructions. Transmitter Vmax must be greater or equal to barrier Vt or Voc,
Transmitter Imax must be greater or equal to barrier It or Isc.
Transmitter Pmax must be greater or equal to barrier Pmax.
Total cable capacitance plus Ci of transmitter shall not exceed Ca of barrier,
Total cable inductance plus Li of transmitter shall not exceed La of barrier.
Vmax >= Voc or Vt
Imax >= Isc or It
Pmax >= Pmax (barrier)
Ci + Ccable <= Ca
Li + Lcable <= La
3
The following temperature ranges are allowed depend on temperature code:
for T12.10.XXX for T12.30.XXX
Temperature ambient Temperature ambient
code temperature range code temperature range
T4 -40 °C to 85 °C T4 -20 °C to 70 °C
T5 -40 °C to 70 °C T5 -20 °C to 70 °C
T6 -40 °C to 60 °C T6 -20 °C to 60 °C
4
Thermometers must be entity - approved by CSA, used in an approved
configuration and installed in accordance with thermometer manufacturer's
instructions. Thermometer Vmax must be greater or equal to transmitter Voc.
Thermometer Imax must be greater or equal to transmitter Isc.
Thermometer Pmax must be greater or equal to transmitter Pmax at output.
Total capacitance of thermometer shall not exceed Ca of transmitter.
Total inductance of the thermometer shall not excced La of transmitter.
5
No revision to drawing without prior CSA approval.