20 WIKA operating instructions model T32.xS
6.3 Conguration
The following parameters can all be congured: sensor model, sensor
connection, user measuring range, output limit, alarm indication,
terminal voltage monitoring, sensor break monitoring, measuring
range monitoring, measuring rate, damping, write protection, oset
values (1-point correction), Tag No. and user linearisation (custom
chararcteristic curve). Furthermore, a linear transformation of the
process value is possible using a 2-point correction.
User linearisation:
Via software, customer-specic sensor characteristics can be stored
in the transmitter in order to dene other sensor types. Number of
auxiliary points: min. 2; max. 30. If more than 2 sensors are connected
(dual sensor function) further congurations can be carried out. With
the dual sensor function, two identical sensors (resistance sensor or
thermocouple) with the same measuring range are connected and
then processed together.
The transmitters are delivered with a basic conguration (see data
sheet TE 32.04) or congured according to customer specications.
If the conguration is changed afterwards, the modications must be
noted on the label using a water-resistant felt-tip pen.
A simulation of the input value is not required to congure
the T32.
A sensor simulation is only required for the functional test.
6. Commissioning, operation
6.2.2 Transmitter in rail mounting version (model T32.3S)
Fasten the rail mounting case (model T32.3S) onto a 35 mm top-hat
rail (EN 60175) by simply locking it into place without the need for any
tools.
Disassembly is achieved by unlocking the locking element.