45
WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
11. Detail setup
11.3 Settingthealarmsignal
Alarmsignaldownscale(3.5mA)
In the event of a failure in the process transmitter, the output signal changes itself to
3.5 mA.
Alarm signal upscale (21.5 mA)
In the event of a failure in the process transmitter, the output signal changes itself to
21.5 mA.
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “Current out” and conrm with [↵].
3. Select “Alarm signal” and conrm with [↵].
4. Select alarm signal and conrm with [↵].
3.5 mA = alarm signal downscale
21.5 mA = alarm signal upscale
Alarm signal is set.
11.4 Settingthesignallimits
The signal limits dene the current range within which the output signal can be. Above
or below the signal limits are the preset limits for the output signal.
Setting range: 3.8 ... 20.5 mA or 4.0 ... 20.0 mA
(NAMUR recommendation for process instruments is 3.8 ... 20.5 mA)
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “Current out” and conrm with [↵].
3. Select “Limits” and conrm with [↵].
3. Select signal limits and conrm with [↵].
Signal limits are set.