Wika UPT-21 Manual do Utilizador Página 47

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 120
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 46
47
WIKA operating instructions process transmitter, model UPT-2x
14068347.01 06/2014 GB/D
GB
11. Detail setup
11.7 SettingtheHART
communication
11.7.1 Settingtheshortaddress(multidropmode)
Setting range: 0 ... 63
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “HART” and conrm with [↵].
3. Select “Short addr. and conrm with [↵].
4. Change digit using [▲] [▼] and conrm with [↵]. The
cursor moves to the next digit. Repeat for each digit.
Short address is set.
11.7.2 Activating/deactivatingconstantcurrent
The constant current aects the output of current values, e.g. in the additional
display
1. Open the operating menu with [↵].
Select “Detail setup" and conrm with [↵].
2. Select “HART” and conrm with [↵].
3. Select “Cons. current” and conrm with [↵].
4. Activate/deactivate constant current.
Select “on” or “o” and conrm with [↵].
Constant current is activated/deactivated.
Vista de página 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 119 120

Comentários a estes Manuais

Sem comentários