WIKA operating instructions model TR33
14073818.01 01/2014 GB/D
23
The measuring range is congurable between -50 ... +250 °C
(-58 ... +482 °F). The conguration software checks the required
measuring range and will only accept permissible values. Intermediate
values are congurable; the smallest increment is 0.1 °C or 0.1 °F. The
thermometers are delivered congured to customer specications within
the congurable limits.
Please note:
The measuring range of the thermometer is limited by the application
range of the measuring element, not by the setting range of the
transmitter.
Maximum permissible temperatures:
■
Without neck tube: -50 … +150 °C (-58 ... +302 °F)
■
With neck tube: -50 … +250 °C (-58 ... +482 °F)
■
At case with transmitter: 85 °C (185 °F)
8. Connecting PU-448 programming unit
7.Conguration/8.ConnectingPU-448...
14004919.01
Connection PU-448 ↔ adapter cable with M12 connector