GB
WIKA operating instructions level sensor model FFG
15
13445627.01 12/2010 GB/D/F
Observe the general prescriptions of installation!
The connections on the separating amplier are marked
accordingly. During connection of the poles, there will be no
current ow.
Potential balance and PE connection
Grounding or potential balance can be via the earth termi-
nal at the bottom side of the probe head.
Protect the probe head against the ingress of water!
Safe sealing of the cable inlet is safeguarded from a
5 mm outer diameter of the cable.
Tighten cable glands. Lock lid of probe head.
Wiring of the level sensor for supplying purposes (in Ex, preferably
blue cable) is by a dual-core cable. The cable cross-section is to be
selected so that the supply voltage to the sensor is no less than 10 V in
the borderline case of maximum current consumption (21.5 mA) with a
given cable length L.
Fig. 4: Electrical connection of the level sensor
5. Electrical connection