Operating InstructionsIndicating and adjustment module for IPT-1* sensors
Dismounting is carried out in reverse order.10 Indicating and adjustment module for IPT-1* sensors4 Mounting31549-EN-081211
5 Set up5.1 Adjustment system1.1231Fig. 4: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] k
5.2 General functionsIPT-1* pressure transmitters have various functions. Hence they canbe adapted to the respective application.Some of these functio
The linearization curve creates a correlation between height andvolume. It takes into account the vessel geometry for the displayedmeasured value and
l Min. and max. temperature2)PointerIn this menu item, the device status is displayed. If the sensor detectsa fault, "OK" will be displayed.
1 Push [OK]2 Select the requested simulation variable with [->] and confirm with[OK]3 Set the requested value with [+] and [->].4 Push [OK]The si
The sensor is already set to the ordered national language. In thismenu item you can change the language. The following languages areavailable, e.g. i
In this menu item, the PIN is activated/deactivated permanently.Entering a 4-digit PIN protects the sensor data against unauthorizedaccess and uninten
l Sensor details, e.g. approval, process fitting, seal, measuring cell,measuring range, electronics, housing, cable entry, plug, cablelength etc.Sensor
Display unitVolumelScaling0 % = 0.0 l100 % = 100.0 lMenu section, serviceIn the menu item "Current output" you determine the behaviour of th
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31.2 Target group . . . . . . . . . . . .
l In the menu item "Failure mode" under "Current output", theparameters "Hold value" and "20.5 mA" are blocked
The channel is the input selector switch for function block (FB) of thesensor. Within the function block, additional scalings (Out-Scale) arecarried o
Here, you determine the unit and scaling for PA-Out. These settingsalso apply to the values displayed on the indicating and adjustmentmodule if in the
5.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1Pointerp-min.: -5.8 mbarp-max.: 167.5 mbarT-min.: -12.5 °CT-max.: +85.5 °C3.2Sensor statu
Indicating and adjustment module for IPT-1* sensors 255 Set up31549-EN-081211
5.6 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Additional PA valueSecondary Value 14.2Out-Scale-UnitVolumel4.3PA-Out-Scale100.00 lin %= 0.0
5.7 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.2SimulationStart simulation▼4.3ResetSelect reset▼4.3LanguageDeutsch4.4Copy sensor dataCopy sen
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
6 Maintenance and fault rectification6.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.6.2 Instrument
7 Dismounting7.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pr essure in t he vessel, high temp
8 Supplement8.1 Technical dataGeneral dataWeight approx. 150 g (0.33 lbs)Ambient conditionsAmbient temperature -15 … +70 °C (+5 … +158 °F)Storage and
8.2 DimensionsIndicating and adjustment module27,6mm(1 3/32")ø66,3mm(2 39/64")45,1mm (1 25/32")9,7mm (3/8")Fig. 5: Indicating and
34 Indicating and adjustment module for IPT-1* sensors8 Supplement31549-EN-081211
Indicating and adjustment module for IPT-1* sensors 358 Supplement31549-EN-081211
WIKA Alexander Wiegand GmbH & Co. KGAlexander-Wiegand-Straße 3063911 Klingenberg/GermanyPhone +49 9372 132295Fax +49 9372 132706e-mail: support-tr
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
2.7 Compatibility according to NAMUR NE 53With respect to compatibility, NAMUR recommendation NE 53 is met.The parameter adjustment of the basic senso
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l Indicating and adjustment modulel Documentation- this operating instructions
12Fig. 2: Rear of the indicating/adjustment module1 Integrated seal ring2 Gold plated contact paths3.2 Principle of operationThe indicating and adjust
3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i
4 Mounting4.1 Mounting stepsThe indicating and adjustment module can be inserted or removed atany time. It is not necessary to interrupt the voltage s