GB
WIKA operating instructions model TR30
11377551.06 07/2014 GB/D
13
Electromagnetic compatibility
(EMC)
2004/108/EC, EN 61326 emission (Group 1,
Class B) and interference immunity (industrial
application)
4)
Electrical connection
M12 x 1 circular connector, 4-pin
Angular DIN connector Form A for cable with
Ø 6 ... 8 mm, cross section max. 1.5 mm²
Readings in % refer to the measuring span
For a correct determination of the overall measuring error, both sensor and transmit-
ter measuring deviations have to be considered.
1)
For detailed specications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.
2)
The temperature transmitter should therefore be protected from temperatures over 85 °C
3)
For measuring spans smaller than 50 K additional 0.1 K
4)
Use resistance thermometers with shielded cable, and ground the shield on at least one end of
the lead, if the cables are longer than 30 m or leave the building.
CE conformity, approvals
CE conformity
EMC directive
5)
2004/108/EC, EN 61326 emission (group 1, class B) and
interference immunity (industrial application)
ATEX directive 94/9/EG (Option)
Approvals (option)
NEPSI Ignition protection type “i” - intrinsic safety,
ignition protection type “iD” - dust protection through
intrinsic safety, China
EAC Import certicate, ignition protection type “i” - intrinsic
safety, ignition protection type “iD” - dust protection
through intrinsic safety, customs union Russia/Belarus/
Kazakhstan
GOST Metrology/measurement technology, Russia
DNV Ships, shipbuilding (e.g. oshore), International
5) Only for built-in transmitter
For further specications see WIKA data sheet TE 60.30.
3. Specications