GB
Thermowell
Stem
Required safety
clearance
11583747.03 10/2013 GB/D/F/E
14 WIKA operating instructions models 53, 54, 55 (ATEX)
CAUTION!
When using thermowells, please
ensure that the stem does not
touch the bottom of the thermowell
since, due to the dierent
expansion coecients of the
materials, the stem may become
buckled at the bottom of the
thermowell.
(Formula for the calculation of
the insertion length l
1
see the
respective thermowell's data sheet)
7. Maintenance and cleaning
7.1 Maintenance
These bimetal thermometers are maintenance-free!
The indicator should be checked once or twice every year. For this
the instrument must be disconnected from the process and checked
using a temperature calibrator.
Repairs must only be carried out by the manufacturer.
7.2 Cleaning
CAUTION!
Clean the thermometer with a moist cloth.
Wash or clean the thermometer before returning it, in
order to protect personnel and the environment from
exposure to residual media.