2.4 Error signaling
The model T32.xS temperature transmitter monitors the connected sensors and its
own hardware for errors. In the event of a known error condition the device generates
an error signalling current.
The response time from the sensor is a maximum of 90 seconds.
This implies the discovery of the following potential errors:
Sensor burnout
Sensor short circuit (only for resistance temperature sensors, not for thermocouples)
Inadmissably high lead resistance (not with duplex resistance temperature sensors)
The online diagnosis-test interval of the instrument should be a maximum of
35 minutes. This implies the discovery of the following potential device errors:
ROM error
EEPROM error
RAM error
Program-counter error
Stack-pointer error
Furthermore, the following monitoring functions are carried out continuously:
Logical program ow control
Internal communications error
Over sensor upper limit
Under sensor lower limit
Cold junction temperature outside permissible limits (only for thermocouples)
Duplex sensor drift monitoring (activated optionally)
Conguration error
Monitoring of the permissible device temperature (optional, activated by default for
SIL versions)
Monitoring of the output limits (optional, not activated by default for SIL versions
starting from 01.01.2011)
CAUTION!
The device's error signalling current (error current) is congured in
accordance with the following requirements:
Error current fail high (high alarm value):
settable in the range ≥ 21.0 mA to ≤ 23.0 mA (upscale)
Error current fail low (low alarm value) :
settable in the range ≥ 3.5 mA to ≤ 3.6 mA (downscale)