Unit of measurement
Density
0001000
kg/dm³
6 Enter the requested density value with [->] and [+], conrm with
[OK] and move to position correction with [->].
The adjustment unit is hence switched over from bar to m.
Proceed as follows to select the temperature unit:
5)
à Activate the selection with [OK] and select "Temperature unit
with [->].
à Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
à Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1 Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Oset
P
=
+0000 mbar
53 mbar
2 Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3 Conrm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1 Edit the % value in the menu item "Min. adjustment" with [OK].
Min. adjustment
+000.0 %
=
+0000.0 mbar
0000.0 mbar
2 Set the requested percentage value with [+] and [->].
3 Edit the requested mbar value with [OK].
4 Set the requested mbar value with [+] and [->].
5)
Selection options: °C, °F.
Carry out position cor-
rection
Carrying out min. ad-
justment
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA/HART 27
6 Set up with the indicating a nd adjustment module