Wika IPT-11 Manual do Utilizador Página 37

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 56
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 36
7 Setup with PACTware and other adjustment
programs
7.1 Connecting the PC
3
1
2
~
=
Power supply
PACTwa re /
DTM
HART-
Modem
TM
Fig. 19: Connecting the PC to the signal cable
1 RS232 connection
2 HART resistor 250 Ω
3 IPT-1* 3
Necessary components:
l IPT-1*
l PC with PACTware and suitable WIKA DTM
l HART modem
l HART resistor approx. 250 Ω
l Power supply unit
Note:
For power supply units with integrated HAR T resistance (inner
resistance approx. 250 Ω), there is no additional external resistance
necessary. Standard Ex separators are often provided with a
suciently high current limitation resistance. In such cases, the
modem can be connected in parallel to the 4 20 mA cable.
7.2 Parameter adjustment with PACTware
Further setup steps are described in the operating instructions manual
"DTM Collection/PACTware" attached to each CD and which can also
be downloaded from our homepage. A detailed description is available
in the online help of PACTware and the WIKA DTMs.
Connecting the PC to
the signal cable
Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor 4 20 mA/HART 37
7 Setup with PACTware and other adjustment programs
31543-EN-090130
Vista de página 36