Dynamic behaviour output
Run-up time approx. 10 s
Fig. 10: Sudden change of the process variable. t
T
: dead time; t
A
: rise time; t
S
: jump response time
1 Process variable
2 Output signal
Dead time ≤ 150 ms
Rise time ≤ 100 ms (10 … 90 %)
Step response time ≤ 250 ms (ti: 0 s, 10 … 90 %)
Damping (63 % of the input variable) 0 … 999 s, adjustable
Input variable
Adjustment
Adjustment range of the min./max. adjustment relating to the nominal measuring range:
- Min. -5 … +95 %
- Max. -5 … +105 %
Adjustment range of the zero/span adjustment relating to the nominal measuring range:
- zero -5 … +95 %
- Span -5 … +105 %
Recommended max. turn down 10 : 1 (no limitation)
Nominal measuring ranges and overload resistance
Nominal range Overload capacity, max.
pressure
Overload capacity, min.
pressure
Gauge pressure
0 … 0.4 bar/0 … 40 kPa 2 bar/200 kPa -1 bar/-100 kPa
0 … 1.6 bar/0 … 160 kPa 10 bar/1000 kPa -1 bar/-100 kPa
0 … 16 bar/0 … 1.6 MPa 80 bar/8 MPa -1 bar/-100 kPa
0 … 40 bar/0 … 4 MPa 80 bar/8 MPa -1 bar/-100 kPa
38 Process pressure transmitter IPT-1* Vers. 3.0 - metalic sensor • 4 … 20 mA