Wika DPT-10 Manual do Utilizador Página 63

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 96
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 62
Fig. 46: Preferred installation for open vessels
I DPT10
II Precipitator
1 Drain valve
6.7 Vent valves on DPT10
A Blocking valve
Proceed as follows:
1 Fill the vessel to just over the lower tap.
2 Fill measuring system with medium.
Open valve A: Medium ows in.
3 Vent instrument
Briey open valve 6, then close it: Fill the measuring instrument
completely with the medium and remove air.
4 Set measurement loop to operation
Now:
Valve A open and valve 6 closed
Then carry out adjustment, see below.
Installation for open
vessels
Prepare the adjustment
Dierential pressure transmitter DPT10 - metal measuring diaphragm Probus PA 63
8 Set up
37245-EN-100120
Vista de página 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 95 96

Comentários a estes Manuais

Sem comentários